I/O compound modules − digital I/O

Eight digital outputs 0.5 A − EPM−S302 and EPM−S305 (NPN)

3

l

93

EDSIO1000 EN 7.0

Technical data

EPM−S302 / EPM−S305 (NPN): rated data

Module identifier

EPM−S302: 262

dec

; EPM−S305: 263

dec

Current consumption/power loss

Current consumption from backplane bus

EPM−S302: 65 mA; EPM−S305: 70 mA

Power loss

EPM−S302: 0.7 W; EPM−S305: 0.6 W

Digital outputs

Number of outputs

8

Cable length

shielded

1000 m

unshielded

600 m

Load voltage

Nominal value

DC 24 (DC 20.4 ... 28.8 V)

Current consumption from load voltage
L+

EPM−S302: 15 mA (without load); EPM−S305: 10 mA (without
load)

Total current

for each group, horizontal structure,
40°C

EPM−S302: 4 A; EPM−S305: 2.5 A

for each group, horizontal structure,
60°C

EPM−S302: 4 A; EPM−S305: 2.5 A

for each group, vertical structure

EPM−S302: 4 A; EPM−S305: 2.5 A

Output voltage

for "1" signal, max. current

Only for EPM−S305: M (+250 mV)

for "1" signal, min. current

Only for EPM−S305: M (+0 V)

Output current

for "1" signal, nominal value

0.5 A

Output delay

from "0" to "1"

30

ms

from "1" to "0"

EPM−S302: 175

ms; EPM−S305: 100 ms

Lamp load

10 W

Parallel switching of outputs

for redundant control

Not possible

for power increase

Not possible

Control of a digital input

Possible

Switching frequencies

for ohmic loads

Max. 1000 Hz

for inductive loads

Max. 0.5 Hz

for lamp loads

Max. 10 Hz

Limitation (internal) of the inductive
breaking voltage

EPM−S302: L+ (−52 V); EPM−S305: +45 V

Short circuit protection of the output

Electronically

Operating threshold of the protection
system

EPM−S302: 1 A; EPM−S305: 1.7 A

Output data size

8 bits

Advertising