2.2.2 Digital Outputs (and Pulsed Outputs)
The WI-I/O-EX-1-S-11 supports up to 16 digital outputs, shared with the digital input

function on the same terminals. The WI-I/O-EX-1-S-12 and WI-I/O-EX-1-S-13 both

provide 8 digital output signals. These signals are marked DIO1-8, and DIO1-16 for the

WI-I/O-EX-1-S-11. On all WI-I/O-EX modules, DIO1-8 can also operate as pulsed

outputs.

When active, digital outputs provide a transistor switch to EARTH. To connect a digital

output, refer to the diagram in Figure 2-6. A bypass diode is recommended to protect

against switching surges for inductive loads such as relay coils.


Figure 2-6: Connection of digital outputs.
Note that digital outputs will only switch DC circuits, with maximum voltage 30VDC.

2.2.3 Analog Inputs
The WI-I/O-EX-1-S-12 provides eight grounded single-ended or four floating differential

analog inputs. These provide measurement of voltage signals (0-10V) or current (0-20

mA) signals. An internal 24V analog loop supply (ALS) is generated for current loops.

Refer to Section 4.4 for detail on configuring single-ended, differential, current-mode or

voltage mode inputs.

_

+

DC

Load

Max 30VDC

0.2A

V-

DIO1

DIO2

EARTH