Weidmuller WI-I/O-EX: Wireless I/O Expansion Modules v1.11 User Manual

Page 53

Advertising
background image

WI-I/O-EX Serial I/O Module

User Manual v1.11

WI-IO-EX Manual v1.11

Page 53

Appendix D. Specifications

EMC Approval

EN 55024:1998

EN 61000-3-2: 2002

EN 61000-3-3: 2002

EN 55022: 1998

FCC Part 15

Operating temperature

range

-40 to +60 deg C

Power supply

10.8 – 30.0 VDC

13.8V / 24VDC nom

Model Dependent. Check

rear label for actual

operating voltages

Supply current (idle 13.8V)

-11

-12

-13

100mA

100mA

120mA

Supply current for I/O

per digital input

per digital output

per analog input

per analog output

13mA

13mA

50mA

50mA

If using 24V loop supply

Loop supply

24V nominal *

* Loop supply will follow

WI-I/O-EX-xx power

supply voltage above 24V

input.

Loop supply max current

WI-I/O-EX-12 : 270mA

WI-I/O-EX-13 : 160mA

RS232 port

ModBus protocol

RS485 port

ModBus protocol

WI-Series protocol

ModBus protocol

Transmission modes

ModBus ASCII 8 data bits

ModBus ASCII 7 data

bits**

ModBus RTU

** If no parity, use 2 stop

bits. If using parity, use 1

stop bit.

Baud rates

1200; 2400; 4800; 9600;

14,400; 19,200; 28,800;

38,400; 57,600; 76,800;

115,200

Parity

Odd, even, none

Stop bits

1, 2

Slave address

01 - 99

Default settings

If slave address = 0

ModBus RTU, 9600, N, 1

Digital inputs