WI-I/O-EX Serial I/O Module

User Manual v1.11

WI-IO-EX Manual v1.11

Page 51

Address Description

40201

Serial port transmission mode

40202

Serial port baud rate

40203

Serial port parity and stop bit

10.

Use the tables below to work out the current communications settings, or write to the

registers using ModScan to change the settings to the desired values. Note that the

module transmission mode should be set to ModBus RTU.

ModBus address 40201, serial port transmission mode:

Setting

Register

Value

ModBus RTU

0x0101

ModBus ASCII, 8 data

bits

0x0201

ModBus ASCII, 7 data

bits

0x0202

ModBus address 40202, serial port baud rate:

Setting

Register

Value

1200

0x000C

2400

0x0018

4800

0x0030

9600

0x0060

14400

0x0090

19200

0x00C0

28800

0x0120

38400

0x0180

57600

0x0240

76800

0x0300

115200 0x0480

ModBus address 40203, serial port parity and stop bit:

Parity Setting

Register’s High Byte

Value

None

0x00

Odd

0x11

Even

0x22

Stop-bit

Setting

Register’s Low Byte

Value

1 stop bit

0x11

2 stop bits

0x22