Weidmuller WI-I/O-EX: Wireless I/O Expansion Modules v1.11 User Manual

Page 28

Advertising
background image

WI-I/O-EX Serial I/O Module

User Manual v1.11

Page 28

February 2010

4.4.1.1 Single-ended voltage input

If the WI-I/O-EX-1-S-12 is to measure voltage with respect to ground, choose the Single-

ended voltage input page, as shown in Figure 4-5.

Remove the access panel from the front of the WI-I/O-EX-1-S-12 case to

gain access to the dip switches. Replace the access panel after setting the

switches.

Set the switches according to the picture shown. The unit should be orientated with the

20-way connector towards you.

Figure 4-5: Setup page for single-ended voltage input.
Once the dip switches on the unit are set, tick the checkbox on the form, and click Save

configuration. Check the WI-I/O-EX Detected panel to ensure that the analog mode has

been updated (to Voltage, single-ended).

Clicking Read from WI-I/O-EX will read the scales out of the unit (if any) and display

them in the scales grid. Note that the dip switches should be set correctly for this result to

be relevant.

Choose the desired scale for each channel in the Scale box. Click the Save scales to WI-

I/O-EX button, and check that the scales are updated in the WI-I/O-EX Detected panel.