4.5.2 Current output
Current outputs may be selected in the scales 0 to 10mA, 0 to 20mA, or 4 to 20mA. For

each scale, the minimum to maximum signal levels are represented by 4000 hex to C000

hex.

Table 4-4 shows how signals from other wireless products translate to WI-I/O-EX-

1-S-13 current levels.

WI-I/O-EX-

1-S-13

Current scale

WI-I/O 9-1

Input current

(mA)

WI-I/O 9-2

Input current

(mA)

WI- GTWY

Register value

(hex)

WI-I/O-EX-1-

S-13

Output current

(mA)

4

4

4000

0

0 to 10mA

20

20

C000

10

4

4

4000

0

0 to 20mA

20

20

C000

20

N/A

*

0

2000

0

2

*

2

3000

2

4

4

4000

4

4 to 20mA

20

20

C000

20

Table 4-4: Compatibility of other products with WI-I/O-EX-1-S-13 voltage outputs.

*

Reduced accuracy for less than 4mA in WI-I/O 9-1.