2.2.3.2 Floating Differential Mode mA Inputs

Differential mode current inputs should be used when measuring a current loop which

cannot be connected to earth or ground. This allows the input to be connected anywhere

in the current loop. Common mode voltage can be up to 27VDC.

Up to four loops can be connected, to terminal pairs [AIN1-AIN2], [AIN3-AIN4],

[AIN5-AIN6], [AIN7-AIN8] - the former terminal is positive and the latter negative.

The diagram in Figure 2-8 indicates how to connect devices for differential mode current

inputs.


Figure 2-8: Connections for differential current inputs.
Note:

-

The module configuration needs to be changed for this type of input

-

To change the input configuration, refer to section 4.4

V-

AIN3

AIN4

AGND

WI-I/O-EX-1-S-12 Module

ALS +24V

Externally powered

sensor

+

-

AIN1

AIN2

+

-

Loop powered

sensor

Power

supply