WI-I/O-EX Serial I/O Module

User Manual v1.11

Page 38

February 2010


Figure 5-2: Check the operation of the WI-I/O-EX-11 module using the DIO Check

page.
Test the digital outputs by setting the select-buttons to ON or OFF - this will force the

DO to the selected state.

Digital inputs are reflected in the software by blacking (ON) or greying (OFF) of the

associated label in the Digital Inputs column.

The pulsed input count values are shown, as well as the pulse rate. The rate can be

viewed in decimal or hexadecimal and represents a fraction of the maximum pulse rate,

where hex 4000 is 0% and hex C000 is 100% of the maximum pulse rate.

The pulse output count values are also shown. The pulse out target may be set by clicking

the Edit Targets button. Pulses will be produced until the count reaches the target.