Rockwell Automation 1395 Digital Reference Adapter Board User Manual

Page 44

Advertising
background image

Chapter 5

Programming Parameters

5-19

Parameter 585 – [A > Digital In 3]
Parameter 535 – [B > Digital In 3]

Use : Maps Digital Input 3
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 12
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 3 (Terminal TB3-45). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (Param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(Param 405). Connecting Digital In 3 to a positive control voltage will
cause the bit specified by this parameter to be set to 1.

Parameter 586 – [A > Digital In 4]
Parameter 536 – [B > Digital In 4]

Use : Maps Digital Input 4
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 14
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 4 (Terminal TB3-46). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast ( param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Connecting Digital In 4 to a positive control voltage will
cause the bit specified by this parameter to be set to 1.

Parameter 587 – [A > Digital In 5]
Parameter 537 – [B > Digital In 5]

Use : Maps Digital Input 5
Programming Terminal units: None
Minimum Value: 0 (#1), 16 (#2)
Maximum Value: 15 (#1), 31 (#2)
Default Value: 5
Description: This parameter performs two functions. It determines
which bit of the two Digital Input Fast parameters will be controlled by
Digital In 5 (Terminal TB3-47). Entering a value of 0 – 15 will control
bits 0 – 15 of the Digital Input 1 Fast (param 400), while entering a
value of 16 – 31 will control bits 0 – 15 of the Digital Input 2 Fast
(param 405). Connecting Digital In 5 to a positive control voltage will
cause the bit specified by this parameter to be set to 1.

Advertising