Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 124

Advertising
background image

6–34

Publication 1336 FORCE–5.13 –– September, 1998

403

Analog Output 2 Scale

[Analog Out 2 Scale]

Analog Out 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 2 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.

Scale Factor

Drive Units

1

32767

1/2

16383

1/4

8192

1/16

2048

Parameter Number

403

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–1

Maximum Value

+1

File – Group

Communication I/O – Analog Output

404

Analog Output 3 Offset

[Analog Out 3 Offset]

Analog Out 3 Offset determines the offset applied to
the Analog Out 3 value after the scale factor is
applied. This allows you to shift the range of the
analog output.

Parameter Number

404

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Output

405

Analog Output 3 Scale

[Analog Out 3 Scale]

Analog Out 3 Scale determines the scale factor or
gain for the Analog In 3 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 3 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.

Scale Factor

Drive Units

1

32767

1/2

16383

1/4

8192

1/16

2048

Parameter Number

405

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–1

Maximum Value

+1

File – Group

Communication I/O – Analog Output

406

Analog Output 4 Offset

[Analog Out 4 Offset]

Analog Out 4 Offset determines the offset applied to
the Analog Out 4 value after the scale factor is
applied. This allows you to shift the range of the
analog output.

Parameter Number

406

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Output