User text string, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 186: User text string read

Advertising
background image

7–40

Publication 1336 FORCE–5.13 –– September, 1998

This read–only message retrieves from the drive the user custom
product name/location test string which identifies the product. The
text string is 16 characters long.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

11 words

Header

Word 1

Header

Word 1

PLC Decimal Value

261

Header

Word 2

Header

Word 3

Header

Word 2

Header

Word 3

PLC Decimal Value

261 –– Message OK

-32507 –– Message Error

Message Structure

Message Length

3

0

0

Product Text

Character 2

Character 1

Data

Word 4

Product Text

Character 4

Character 3

Data

Word 5

Product Text

Character 6

Character 5

Data

Word 6

Product Text

Character 8

Character 7

Data

Word 7

Product Text

Character 10

Character 9

Data

Word 8

Product Text

Character 12

Character 11

Data

Word 9

Product Text

Character 14

Character 13

Data

Word 10

Product Text

Character 16

Character 15

Data

Word 11

0

PLC Request –– Block Transfer Write

Drive Response –– Block Transfer Read

Message Operation

This operation reads your custom product test string stored in the
drive. The response message returns this information beginning with
data word 4. The text string is returned with each data word
containing two ASCII characters per word. This data returns with the
first and second characters in opposite order as shown in the
example.

User Text String

User Text String Read

Advertising