Before you can transfer data between the PLC Communications
Adapter Board and the analog I/O, you need to do the following:

1. Hard wire the analog I/O to the PLC Communications Adapter

Board terminals.

2. Set up the analog input and output configuration parameters in

the drive.

3. Create any user links, if appropriate.

Note: The PLC Communications Adapter Board has been
pre–configured for your convenience. The pre–configured links are
listed later in this chapter.

Each terminal has parameters associated with it as shown here in the
analog I/O block diagram.

+10V REF

17

REF COM

18

–10V REF

19

OUT1

1

Par 401 Scale

COM1

2

Par 400 Offset

TB21

Analog Out #1

Analog Out 1

OUT2

3

Par 403 Scale

COM2

4

Par 402 Offset

Analog Out #2

Analog Out 2

OUT3

5

Par 405 Scale

COM3

6

Par 404 Offset

Analog Out #3

Analog Out 3

OUT4

7

Par 407 Scale

COM4

8

Par 406 Offset

Analog Out #4

Analog Out 4

339

IN1+

9

Par 393 Scale

IN1–

10

Par 392 Offset

Analog In #1

Analog In 1

340

IN2+

11

Par 395 Scale

IN2–

12

Par 394 Offset

Analog In #2

Analog In 2

341

IN3+

13

Par 397 Scale

IN3–

14

Par 396 Offset

Analog In #3

Analog In 3

342

IN4+

15

Par 399 Scale

IN4–

16

Par 398 Offset

Analog In #4

Analog In 4

Power
Supply

387

388

390

389