Warning queue, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 169: Warning clear

Advertising
background image

7–23

Publication 1336 FORCE–5.13 –– September, 1998

The Warning Clear message issues either a Clear Fault/Warning
command or a Clear Warning Queue command to the drive.

PLC Block Transfer Instruction Data

BTW instruction length:

4 words

BTR instruction length:

4 words

Header

Word 1

Header

Word 1

PLC Decimal Value

-30720

Header

Word 2

Header

Word 2

Data

Word 3

PLC Decimal Value

2048 –– Message OK

0

-30720 –– Message Error

Message Structure

Message Length

4

0

Header

Word 3

0

Header

Word 4

PLC Request –– Block Transfer Write

Not Used

Warning Command

Clear Fault/Warning
Clear Warning Queue

EE Command

Value

00
01
02

Message Request

This bit indicates the status of the
request.

Message OK

Warning Command RET

Message Error

Value

0
1

Message Request

Data

Word 4

This bit indicates the status of the
response.

EE Command

Drive Response –– Block Transfer Read

Message Operation

The Warning Clear function specified in the BTW sends a warning
fault handling request to the drive. Word 4 of the BTW defines
which handling option is requested:

If word 4 has a value of 1, this message clears the last fault.

If word 4 has a value of 2, this message clears the entire warning
fault queue.

If an error has occurred in the request, word 2 of the BTR returns a
value of -30975. Word 4 of the BTR responds to the request of BTW
word 4.

Warning Queue

Warning Clear

Advertising