The PLC Communications Adapter Board contains four trend buffers
that you can set up to monitor any parameter. Each buffer can store
up to 500 data points.

Parameters 454 through 493 are associated with trending:

Parameter

number:

Parameter

name:

Specifies:

454, 464,
474, 484

Trend Input

The data value to sample at the specified trend
sample rate. You should link this parameter to
the parameter that is to be sampled.

455, 465,
475, 485

Trend Operand
Parameter X
(Operand X)

The first half of the trend trigger evaluation.
This parameter is generally linked to another
parameter.

456, 466

,

476, 486

Trend Operand
Parameter Y
(Operand Y)

The second half of the trend trigger evaluation.
This parameter can either be a constant value
or linked to another parameter.

457, 467,
477, 487

Trend Operator

The operator used for the trend trigger
evaluation, which compares Operand X to
Operand Y.

458, 468,
478, 488

Trend Sample Rate

The interval at which the data in the Trend
Input parameter is sampled.

459, 469,
479, 489

Trend Post
Samples

The number of data samples for the Trend
Input parameter to gather once the trigger
evaluation becomes true.

460, 470,
480, 490

Trend Continuous
Trigger

Whether a single trend operation (one–shot) or
a continuous trend operation is performed.

461, 471,
481, 491

Trend Select

The trend mode to use. The trend mode may
be enable a trend, disable a trend, or force a
trigger condition

462, 472,
482, 492

Trend Status

Which state the trend is currently in. The trend
states are Stopped, Forced Trigger, Running,
and Tripped Trigger.

463, 473,
483, 493

Trend Outpu

t

The last 500 data values once the trigger
condition is true and all post samples are
gathered.

➀ The parameters for the four trend buffers behave in the same way.
Therefore, the parameter names listed in this chapter are listed
generically. For example, Tr1 Opnd Parm X is listed as Trend
Operand Parameter X, or Operand X.

For more information about the trending parameters, refer to Chapter
6, Parameters.

Using Trend Parameters

"