Channel A Status D8, D10, and D12
Channel B Status D13, D14, and D15

These LEDs reflect the operational status of either RIO or DH+
communications.

LED:

State:

RIO Adapter Function:

RIO Scanner Function:

DH+ Function:

D8 and D13
(Red)

LED on

Hardware malfunction

Hardware malfunction

Domino plug
malfunction

LED off

Communications loss or
D12 and D15 on.

None

None

LED
blinking

A PLC or RIO scanner
has the rack inhibited or
the PLC is in Reset/
Program/Test mode

All devices in the scan
list are faulted

Duplicate node on DH+
link

D10 and
D14

LED on

None

None

Normal DH+
communications

(Yellow)

LED off

None

None

PLC Communications
Adapter Board faulted

LED
blinking

None

None

No communications
over DH+

D12 and
D15

LED on

Normal PLC controller
communications

All devices in the scan
list are operational

None

(Green)

LED off

No communications to
PLC control or D8 and
D13 on

No communications to
PLC control or D8 and
D13 on

None

LED
blinking

PLC in Reset/Program/
Test mode or PLC has
rack inhibited

At least one device on the
scan list is faulted. For
example, if you turn one
half rack off, this light
blinks.

None