Installation

4-9

3. Route the new wire harness along the low voltage door to the 825

Plus. (Figure 4.23)

4. Cut, strip, and connect each numbered wire to the corresponding

numbered green 825 Plus terminal plug.

5. Route the black converter module cable along the low voltage door

and plug the telephone style connector to the back of the 825 Plus.

Refer to the supplied wiring diagram during

installation of 825 Plus Interface Panel. Refer to the
Ordering Information section for Electrical Diagram
(ED) drawing number.

6. If the RTD option is used, refer to the 825 Plus RTD Scanner

Installation Guide (Appendix C) for additional information.

Failure to reconnect all wires and cables correctly
may result in equipment damage, personal injury
and/or death.

A T T E N T I O N

A T T E N T I O N

I M P O R T A N T

I M P O R T A N T

Figure 4.23