Rockwell Automation 1500 Modular Protection System Conversion Kit (Bulletin 1406 to Bulletin 825 Plus) User Manual
Page 23
Advertising
1500-IN058D-EN-E – June 2013
Installation
4-11
8. Test the control circuit functionality by electrically operating the
contactor (air or vacuum) in test mode (Figure 4.26). This may
require the use of test jumpers depending on the control circuit.
Refer to original drawings supplied with the equipment.
9. Program the 825 Plus with the correct motor and protection
parameters (Figure 4.27).
Refer to the User Manual publication 825-UM004_-EN-P
included with the 825 Plus for programming instructions.
10. Turn test switch to OFF. Return the controller to service by
removing any test voltage supply and turning the selector switch
back to the "NORMAL" position.
11. Close the low voltage door and tighten down the door screws.
Figure 4.27
Figure 4.26
Advertising