1500-IN058D-EN-E – June 2013

Installation

4-11

8. Test the control circuit functionality by electrically operating the

contactor (air or vacuum) in test mode (Figure 4.26). This may
require the use of test jumpers depending on the control circuit.
Refer to original drawings supplied with the equipment.

9. Program the 825 Plus with the correct motor and protection

parameters (Figure 4.27).

Refer to the User Manual publication 825-UM004_-EN-P
included with the 825 Plus for programming instructions.

10. Turn test switch to OFF. Return the controller to service by

removing any test voltage supply and turning the selector switch
back to the "NORMAL" position.

11. Close the low voltage door and tighten down the door screws.