Function Description

Bul. 1406 Parameters

Bul. 825 Plus Parameters

Jam Protection

Yes

Yes

Undervoltage Protection

Yes n Ye

s

Ground Fault Alarm Current

1A – 25A

0.01 – 25A

Ground Fault Trip Current

1A – 25A

0.25A – 25A

Ground Fault Trip Time

10 ms – 1 s

0 – 5s

Short Circuit Protection

No

Yes

Jam Trip Current

2-10 (multiple of FLC)

1-6 (multiple of FLC)

Underload Trip Current

50 – 90 (percent of FLC)

10 – 100 (percent of FLC)

Underload Trip Time Delay

1s – 10s

0 – 120s

Ultimate Trip Current

100 – 125 (percent of FLC)

4 – 12 (multiple of FLC)

Winding Alarm Temperature

20

o

C – 180

o

C

0 – 250°C

Winding Trip Temperature

20

o

C –180

o

C 0

– 250°C

Bearing Alarm Temperature

20

o

C –180

o

C 0

– 250°C

Bearing Trip Temperature

20

o

C –180

o

C

0 – 250°C

Ambient Temperature Sensor Input

No

Yes

Reset Condition

Auto/Manual

Auto/Manual

Speed Switch Input

Yes

Yes o

Analog Output

No

Yes

Communication P

LC only

DeviceNet, Remote I/O,

PROFIBUS, Modbus

Trip Contacts

2 form-C contacts (fail safe)

2 form-C contacts (fail safe)

Alarm Contacts

2 form-C contacts (fail safe)

2 form-C contacts (fail safe)

™