RTD Interface Panel • Installation Guide

Failure to follow these steps can result in damage to the
equipment and/or personal injury.

1. Ensure the RTD wires are disconnected from the 1406 RTD module.

Using the wire number table in Appendix C, mark each wire with the
corresponding 1406 RTD module terminal block number.

2. Remove the 1406 RTD module from the low voltage panel. Save all

the mounting hardware.

3. Using the mounting hardware saved in the previous step, mount the

825 Plus RTD Panel in the location vacated by the 1406 RTD module.

4. Reconnect the RTD wires to the corresponding 825P RTD Panel

terminal blocks.

5. Using the spiral wrap provided, combine the existing and RTD

Scanner fiber-optic communication link to the back of the 825 Plus.