Checking module calibration – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 12

Advertising
background image

1–2

Calibrating Your Module

Publication 1771Ć6.5.116 - July 1996

If a calibration check of your module becomes necessary:

1. Verify that the module is in voltage mode. In single-ended mode,

apply voltages to channels 1 through 16.

2. Send a configuration block transfer write to the module that

replicates the specific application. (This forces the module to do
an internal calibration.)

3. Apply –10V, –5V, –2.5V 0V, 1V, 2.5V, 5V, and 10V to the

module. In differential, apply voltages to channels 1 through 8

Verify that the values returned are within 0.1% of bipolar full
scale.

Range

Scaling

Accuracy (V/mA)

0 to 5V

0, 5000

1 to 5V

1000, 5000

+0.010V

-5 to +5V

-5000, 5000

-10 to +10V

-9999, 9999

+0.020V

4 to 20mA

400, 2000

0 to 20mA

0, 2000

+0.04mA

-20 to +20mA

-2000, 2000

Range

Error (counts) (no scaling)

0 to 5V

+4

1 to 5V

+4

-5 to +5V

+8

-10 to +10V

+8

4 to 20mA

+4

0 to 20mA

+4

-20 to +20mA

+4

4. If values are within tolerance, no calibration is necessary. If not,

perform calibration below.

Checking Module

Calibration