Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 41

Advertising
background image

4-11

Publication 1771Ć6.5.116 - June 1996

Figure 4.4

Connection Diagram for 8 Differential Inputs and FourĆWire Transmitters

Channel 1+
Channel 1Ć
Channel 2+
Channel 2Ć

Channel 3+
Channel 3Ć
Channel 4+
Channel 4Ć

Channel 5+
Channel 5Ć
Channel 6+
Channel 6Ć

Channel 7+
Channel 7Ć
Channel 8+
Channel 8Ć
Module Common

Not used

Not used

Not used

Module Common

Source Ground

1

. Unused channels must have their + and Ć inputs jumpered

together and tied to module common to reduce noise.

1771ĆWG

Field Wiring Arm

1
2

3

4

5

6
7

8
9

10

11
12

13

14
15

16

17
18

19

20
21

10949-I

NOTE:

The 1771ĆIFF module does not supply loop power for the input device. The user must supply

loop power for loopĆpowered input devices.

+

-

Configuring the module for differential inputs does not provide isolation.

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771

I/O chassis

extend up to the point of termination

Important: The shield should extend to the termination point,

exposing just enough cable to adequately terminate the

inner conductors. Use heat shrink or another suitable

insulation where the wire exits the cable jacket.

+

-

Power

Supply

4ĆWire

Transmitter

Power

Supply

4ĆWire

Transmitter

2

Tie power supply grounds together to

minimize ground loops.

Note: Refer to transmitter manufacturers

specifications for power supply connections.