Scan time is defined as the amount of time it takes for the input
module to read the input channels and place new data into the data
buffer.

Word 24 of the block transfer write data table shows the scan time
for the module for the given configuration. These figures are the time
it takes to sample all channels and process the data. Refer to
Appendix A for tables showing common scan times at various
oversample rates.

Table 10.A

Scan Time in SingleĆEnded Mode

Number of

Oversamples

Word 24

Time (ms)

0

798

7.98

1

392

3.92

2

451

4.51

4

567

5.67

8

798

7.98

16

1260

12.60

32

2183

21.83

64

4028

40.28

128

7718

77.18

256

15100

151.00

Table 10.B

Scan Time in Differential Mode

Number of

Oversamples

Word 24

Time (ms)

0

402

4.02

1

199

1.99

2

229

2.29

4

287

2.87

8

402

4.02

16

634

6.34

32

1096

10.96

64

2018

20.18

128

3864

38.64

256

7554

75.54