Publication 1771Ć6.5.116 - June 1996

Figure 4.2

Connection Diagram for 16 SingleĆended Inputs and

FourĆWire Transmitters

1

All commons are electrically tied

together inside the module.

2

Jumper all unused channels to

module common to reduce noise.

Source Ground

Channel 1
Channel 2

2

Channel 3

Channel 4

Channel 5
Channel 6
Channel 7
Channel 8

Channel 9
Channel 10
Channel 11
Channel 12

Channel 13
Channel 14
Channel 15
Channel 16

1

Module Common

1

Module Common

1

Module Common

1

Module Common

1

Module Common

1771ĆWG

Field Wiring Arm

1
2
3
4
5

6
7

8
9

10

11
12
13

14
15

16

17
18

19
20
21

10948ĆI

The 1771ĆIFF module does not supply loop power for the input device. The user must supply

loop power for loopĆpowered input devices.

+

-

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771

I/O chassis

extend up to the point of termination

Important: The shield should extend to the termination point,

exposing just enough cable to adequately terminate the

inner conductors. Use heat shrink or another suitable

insulation where the wire exits the cable jacket.

Power

Supply

4ĆWire

Transmitter

+

-

Power

Supply

4ĆWire

Transmitter

3

Tie power supply grounds together to

minimize ground loops.

Note: Refer to transmitter manufacturers

specifications for power supply connections.