Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual
Page 19
Advertising
Off
On
Legend
Blinking
2–3
Troubleshooting Your Input Module
Publication 1771Ć6.5.116 - July 1996
The following table lists the probable cause and recommended
actions for some common trouble indications.
Troubleshooting Chartfor the FastAnalog InputModule (1771ĆIFF/A)
Indicators
Probable Cause
Recommended Action
RUN (green)
FLT (red)
Normal operation
None
RUN (blinking)
FLT (off)
Awaiting configuration Block Transfer
Write
Sendconfiguration BTW
RUN (green)
FLT (red)
Hardware failure in module
Return module for repair
RUN
Neither LED
FLT
comes on
No power
Turn off power. Remove andreinsert
module into chassis. Return power.
If problem still exists, andchassis power
supply is functioning properly, return the
module for repair.