Troubleshooting Your Input Module

Publication 1771Ć6.5.116 - July 1996

The following table lists the probable cause and recommended
actions for some common trouble indications.

Troubleshooting Chartfor the FastAnalog InputModule (1771ĆIFF/A)

Indicators

Probable Cause

Recommended Action

RUN (green)

FLT (red)

Normal operation

None

RUN (blinking)

FLT (off)

Awaiting configuration Block Transfer

Write

Sendconfiguration BTW

RUN (green)

FLT (red)

Hardware failure in module

Return module for repair

RUN

Neither LED

FLT

comes on

No power

Turn off power. Remove andreinsert

module into chassis. Return power.

If problem still exists, andchassis power

supply is functioning properly, return the

module for repair.