Data first configuration – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 66

Advertising
background image

7-4

Publication 1771Ć6.5.116 - May 1996

When bits 9 and 10 in block transfer write word 3 are set for “two’s
complement – data first configuration,” the block transfer read will
have the channel data first in the transfer.

Figure 7.2

BlockTransfer Read in Two's Complement - Data First Configuration, SingleĆended

Inputs

Dec. Bits

15 14 13 12 11 10 09 08 07 06 05 04

03

02

01

00

Description

Octal Bits

17 16 15 14 13 12 11 10 07 06 05 04

03

02

01

00

Description

Word 1

Channel 1 Input

Channel 1 Input

2

Channel 2 Input

Channel 2 Input

3

Channel 3 Input

Channel 3 Input

4

Channel 4 Input

Channel 4 Input

16

Channel 16 Input

Channel 16 Input

17

HF EE CS RTS IS OR PU

Diagnostics

18

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data underrange for channels 1-16

1

19

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data overrange for channels 1-16

1

20

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data polarity for channels 1-16

21

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Offset Calibration Results

22

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Gain Calibration Results

23

15Ćbit rolling counter - binary, 1ms resolution

Time Stamp

24

Update rate - binary, to 1

υ

s, with +4

µ

s resolution

Scan Time

Where:

PU = Power up bit

OR= Out of range bit

IS = Invalid scaling bit

RTS = Real time sampling bit

HF = Hardware Fault

EE = EEPROM status bits

CS = Calibration status bits

1

These bits are set (1) at approximately the input range limits selected (Table NO TAG).

Data First Configuration