Plcć3 programming – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 47

Advertising
background image

Module Programming

5-3

Publication 1771Ć6.5.116 - July 1996

Block transfer instructions with the PLC-3 processor use one binary
file in a data table section for module location and other related data.
This is the block transfer control file. The block transfer data file
stores data that you want transferred to your module (when
programming a block transfer write) or from your module (when
programming a block transfer read). The address of the block
transfer data files are stored in the block transfer control file.

The industrial terminal prompts you to create a control file when a
block transfer instruction is being programmed. The same block
transfer control file is used for both the read and write
instructions for your module.
A different block transfer control file
is required for every module.

A sample program segment with block transfer instructions is
shown below.

Figure 5.2

PLCĆ3 Family Sample Program Structure

Block Transfer

EN

BLOCK XFER READ

RACK:

GROUP:

MODULE:

DATA:

LENGTH =

CNTL:

XXX

X

X=XXXX

XXXXX=XXXX

X

XXXXX:XXXX

ENABLE

12

DN

DONE

15

Done Bit

Pushbutton

Power-up

Bit

EN

ENABLE

02

ER

ERROR

03

Block Transfer

Write

Done Bit

DN

DONE

05

1

2

BLOCK XFER WRITE

RACK :

GROUP :

MODULE:

DATA:

XXX

X

X = XXXX

XXXXX = XXXX

LENGTH =

CNTL:

X

XXXXX:XXXX

ER

ERROR

13

10955ĆI

At powerĆup, the user program examines,

the BTR done bit in the block transfer read

file, initiates a block transfer write to

configure the module, and then does

consecutive block transfer reads

continuously. The powerĆup bit can be

examined and used anywhere in the

program.

Rungs 1 and 2

Rungs 1 and 2 are the block transfer read

and write instructions. The BTR done bit in

rung 1, being false, initiates the first read

block transfer. After the first read block

transfer, the module performs a block

transfer write and then does continuous

block transfer reads until the pushbutton is

used to request another block transfer write.

After this single block transfer write is

performed, the module returns to continuous

block transfer reads automatically.

Program Action

Read

BTR

BTW

PLCĆ3 Programming