2 – install your armorblock module, Overview, Install the module – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual

Page 15: Set the network address, Chapter 2, Install your armorblock module, Overview install the module, Chapter

Advertising
background image

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

7

Chapter

2

Install Your ArmorBlock Module

Overview

This chapter shows you how to install and wire the 1732E ArmorBlock
EtherNet/IP Dual Port 4-Point Thermocouple and RTD Input modules. The
only tools you require are a flat or Phillips head screwdriver and drill. This
chapter includes the following topics:

Install the Module

To install the module:

• Set the network address
• Mount the module
• Connect the I/O, Network, and Auxiliary cables to the module.

Set the Network Address

The I/O block ships with the rotary switches set to 999 and DHCP enabled. To
change the network address, you can do one of the following:

• adjust the node address switches on the front of the module.
• use a Dynamic Host Configuration Protocol (DHCP) server, such as

Rockwell Automation BootP/DHCP.

• retrieve the IP address from nonvolatile memory.

The I/O block reads the switches first to determine if the switches are set to a
valid number. To set the network address:

1.

Remove power.

2.

Remove the switch dust caps.

3.

Rotate the three (3) switches on the front of the module using a small
blade screwdriver.

4.

Line up the small notch on the switch with the number setting you wish to
use.
Valid settings range from 001…254.

Topics

Page

Install the Module

7

Set the Network Address

7

Mount the Module

9

Wire the Module

10

Advertising
This manual is related to the following products: