Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

31

Configure Your Thermocouple and RTD Input Modules with RSLogix 5000 Software Chapter 3

To configure the Ethernet ports, click the Port Configuration tab.
This tab is only available for editing when the device is online.

To configure the ports:

Calibration Tab

The Calibration tab on the Module Properties dialog box lets you recalibrate the
module, if necessary. Calibration corrects any hardware inaccuracies on a
particular channel.

Calibration is available on a per-channel basis for both Thermocouple and RTD
modules. Calibration points for the Thermocouple module is 0 and 78.125 mV
for each channel. For the RTD module, calibration endpoints are dependent on
the sensor type configured for each channel.

For a step-by-step guide on how to calibrate your modules, see

Calibrate Your

Modules on page 45

.

To

Then

Use the default port speed and duplex settings

Leave Auto-negotiate port speed and duplex
checked. This setting determines the actual speed
and duplex setting.

Manually configure your port’s speed and
duplex settings

Follow these steps.
1. Clear the Auto-negotiate port speed and duplex

checkbox.

2. From the Current Port Speed pull-down menu,

choose a port speed.

3. From the Current Duplex pull-down menu,

choose the appropriate Duplex value, that is,
Half Duplex or Full Duplex.

IMPORTANT

Consider the following when you configure the module’s port settings:

If the module is connected to an unmanaged switch, leave Auto-negotiate port

speed and duplex checked or the module will fail.

If you are forcing the port speed and duplex with a managed switch, the

corresponding port of the managed switch must be forced to the same settings or
the module will fail.