Wire the module, I/o connectors – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual

Page 18

Advertising
background image

10

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

Chapter 2 Install Your ArmorBlock Module

and the lock washer as shown in the mounting illustration. Torque the mounting
screws to 0.68 Nm (6 lb-in.).

High Vibration Area Mounting

Wire the Module

The 1732E-IT4IM12R and 1732E-IR4IM12R modules have 5-pin micro-style
M12 I/O connectors. We provide caps to cover the unused connectors on your
module. Connect the quick-disconnect cord sets you selected for your module to
the appropriate ports.

I/O Connectors

(1)

Micro-style M12 5-Pin Input Female Connector – 1732E-IT4IM12R

Micro-style M12 5-Pin Input Female Connector – 1732E-IR4IM12R

45768

Lock washer

Flat washer

(1) Only 4 of the 5 pins are active. The center pin (5) is internally tied to signal ground to minimize

external noise pickup.

3

4

1

2

5

45868

(View into connector)
Pin 1CJC +
Pin 2TC +
Pin 3CJC -
Pin 4TC -
Pin 5No Connect

A

C

B

3

4

1

2

5

45868

(View into connector)
Pin 1No Connect
Pin 2A
Pin 3B
Pin 4C
Pin 5No Connect