Calibrate the rtd module – Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD User Manual

Page 57

Advertising
background image

Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

49

Calibrate Your Modules Chapter 5

Calibrate the RTD Module

The 1732E-IR4IM12R does not calibrate for voltage or current. It uses two
precision resistors to calibrate the channels in ohms. The module has a preset
calibration points for the sensor type configured for each input channel,

Perform the calibration process through the RSLogix 5000 software.

While you are online, you must access the Calibration tab on the Module
Properties dialog box. See

Edit Your Module Configuration on page 21

.

1.

Click Calibration Tab on the Module Properties dialog box.

2.

Check the Calibrate checkbox to specify which channel to calibrate.
In this example, check Channels 0…3.

3.

Under Calibrate Channels select One At a Time.

4.

Click Start Calibration, which is active when:
• the system is online, and
• you selected at least one of the channels.

Calibration Points for the RTD Module

RTD Sensor Type

Calibration Points

Ohms

0 and 500 Ohms

100

Ω

Pt 385

0 and 500 Ohms

200

Ω

Pt 385

0 and 1000 Ohms

100

Ω

Pt 3916

0 and 500 Ohms

200

Ω

Pt 3916

0 and 1000 Ohms

10

Ω

Cu 427

0 and 64.9 Ohms

120

Ω

Ni 672

0 and 500 Ohms

100

Ω

Ni 618

0 and 250 Ohms

120

Ω

Ni 618

0 and 250 Ohms

Choose whether to calibrate each

channel one at a time or in groups all

at once

Advertising
This manual is related to the following products: