Chapter 4 Configurable Features for the Thermocouple and RTD Input Modules

Chapter Summary

This chapter discussed the different configurable features and their effect on all
input channels for both Thermocouple and RTD modules.

1732E-IR4IM12R – Produced Data Structure for RTD Input

Configuration
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0…3

Reserved (must be zero)

4…5

Channel 0 Data

6…7

Channel 1 Data

8…9

Channel 2 Data

10…11

Channel 3 Data

12

Channel 0 Status

(1)

(1) This parameter is in Byte and has the following structure:

Bit 0 = Fault; Bit 1 = Calibration; Bit 2 = Low Alarm; Bit 3 = High Alarm; Bit 4 = Low Low Alarm; Bit 5 = High High
Alarm; Bit 6 = Underrange; Bit 7 = Overrange

13

Channel 1 Status

(1)

14

Channel 2 Status

(1)

15

Channel 3 Status

(1)