Chapter 5 Calibrate Your Modules

8.

Set the calibrator for the high reference voltage and apply it to the module
The Input Calibration - High Value dialog appears.

9.

From the High Value dialog, click Next to start calibration.
The Input Calibration - Results dialog appears. It shows you the results of
calibration.

• For failed calibration, go to step

10

.

• For successful calibration, go to step

11

.

10.

If the calibration failed, click Retry to recalibrate the same channel.
This takes you back to steps

6

9

until you get successful calibration on the

channel.

11.

If the calibration is successful, click Next to start calibration on the next
channel (in this example, channel 1).
This takes you back to steps

6

9

.

12.

After successful calibration on the channel(s), click Finish to close the
Calibration Wizard.

TIP

If several channels have been selected for calibration with One At a Time
option enabled, only one channel will appear in the list at the first round
(low reference and high reference) of calibration.

TIP

If calibration is configured to be done In Groups, the High Value dialog
box shows all the channels enabled for calibration.

TIP

Cold junction compensation calibration follows the same steps, with
resistance used on the thermistor connections.