Rockwell Automation Publication 1732E-UM004A-EN-E - July 2012

Appendix A Specifications

The 1732E-IR4IM12R RTD input module has the following input
specifications.

Thermocouple types

Type

Material

Temperature
Range °C (°F)

Voltage
Range (mV)

B

Pt /30% Rh vs. Pt/
5% Rh

40…1820
(104…3308)

0…13.820

C

W/5% Re vs. W/
26% Re

0…2320
(32…4208)

0…37.107

E

Ni/Cr vs. Cu/Ni

-270…1000
(-454…1832)

-9.835…76.373

J

Ni/Cr vs. Cu/Ni

-210…1200
(-346…2192)

-8.095…69.553

K

Ni/Cr vs. Ni/Al

-270…1372
(-454…2501.6)

-6.458…54.886

N

Ni/14.2%Cr/1.4%Si
vs. Ni/4.4%Si/
0.1%Mg

-270…1300
(-454…2372)

-4.345…47.513

R

Pt/13%Rh vs. Pt

-50…1768
(-58…3214.4)

-0.226…21.101

S

Pt/10%Rh vs. Pt

-50…1768
(-58…3214.4)

-0.236…18.693

T

Cu vs. Cu/Ni

-270…400
(-454…752)

-6.258…20.872

Cold junction compensation

Rockwell Automation 871A-TS4CJC-DM, 871A-TR4CJC-DM

Cold junction compensation
range

0…70 °C (32…158 °F) for 302 type thermistors

Thermistor types supported

Thermometrics MF65F302V/W or DC95F302V/W

Input voltage range

±78 mV, 1 mW

Accuracy

0.1% Full Scale @ 25 °C (77 °F)

Accuracy drift with
temperature

30 ppm % Full Scale /°C @ 25 °C (77 °F)

Calibration

Factory calibrated. Calibration is also supported through
RSLogix 5000.

Common mode rejection rate

120 dB @ 50/60 Hz

Normal mode rejection rate

100 dB @ 50/60 Hz

Sample Rate Filters

(1)

50 Hz
60 Hz
250 Hz
500 Hz

(1) Sample Rate/Notch Filter Frequency, selectable per channel.

Input Specifications – 1732E-IR4IM12R

Attributes

Value

Number of inputs

4, isolated

Resolution, min

16 bits

Input Specifications – 1732E-IT4IM12R