GV3000/SE AC Drive Hardware Reference, Version 6.06

5.2 Installing Fuses for Branch Circuit Protection

Install the required, user-supplied branch circuit protection fuses according to the

applicable local, national, and international codes (e.g., NEC/CEC). The fuses must

be installed in the line before the drive input terminals. See figures 5.1 and 5.2. Fuse

value selections are provided in table 3.12.

5.3 Installing a Required External/Separate Input

Disconnect

An input disconnect must be installed in the line before the drive input terminals in

accordance with local, national, and international codes (e.g., NEC/CEC). The

disconnect should be sized according to the in-rush current as well as any additional

loads the disconnect might supply. The trip rating for the inrush current (10-12 times

full load current) should be coordinated with that of the input isolation transformer, if

used. Refer to section 5.1 for additional information. Note that 200-400 HP drives may

be supplied with an optional AC disconnect.

Table 5.1 – AC Line Reactors

Drive

Line Reactor Inductance (+/-10%)

1 HP

12.0 mh

2 to 3 HP

6.5 mh

5 HP

3.0 mh

7.5 HP

2.5 mh

10 HP

1.5 mh

15 HP

1.2 mh

20 to 25 HP

0.8 mh

30 HP

0.7 mh

40 HP

0.5 mh

50 to 60 HP

0.4 mh

200 to 400 HP

30

µ

h

!

ATTENTION: Most codes require that upstream branch protection be

provided to protect input power wiring. Failure to observe this precaution

could result in severe bodily injury or loss of life.