Completing the Installation

8-1

C

HAPTER

8

Completing the Installation

This chapter provides instructions on how to perform a final check of the installation

before power is applied to the drive.

8.1 Checking the Installation

Use the following procedure to verify the condition of the installation:

Step 1. Turn off, lock out, and tag the input power to the drive. Wait five minutes.
Step 2. Verify that the DC bus voltage is zero. Refer to section 9.3.
Step 3. If a function loss coast-stop pushbutton has been installed, verify that it has

been wired correctly. Be sure the factory-installed jumper at terminals 16 and

20 (or 16A and 20A) has been removed so that the coast-stop pushbutton

will work.

Step 4. Remove any debris, such as metal shavings, from around the drive.
Step 5. Check that there is adequate clearance around the drive.
Step 6. Verify that there is nothing mounted behind the drive.
Step 7. Verify that the wiring to the terminal strip and the power terminals is correct.
Step 8. Check that the wire size is within terminal specification and that the wires are

tightened properly.

Step 9. Check that user-supplied branch circuit protection is installed and correctly

rated.

!

ATTENTION: Only qualified electrical personnel familiar with the

construction and operation of this equipment and the hazards involved

should start and adjust it. Read and understand this manual in its entirety

before proceeding. Failure to observe this precaution could result in

severe bodily injury or loss of life.

!

ATTENTION: DC bus capacitors retain hazardous voltages after input

power has been disconnected. After disconnecting input power, wait five

(5) minutes for the DC bus capacitors to discharge and then check the

voltage with a voltmeter to ensure the DC bus capacitors are discharged

before touching any internal components. Failure to observe this

precaution could result in severe bodily injury or loss of life.

!

ATTENTION: The user must provide an external, hardwired emergency

stop circuit outside of the drive circuitry. This circuit must disable the

system in case of improper operation. Uncontrolled machine operation

may result if this procedure is not followed. Failure to observe this

precaution could result in bodily injury.