Installing Output Power Wiring

6-1

C

HAPTER

6

Installing Output Power Wiring

This chapter provides instructions on wiring output contactors, motor overload

protection, and output wiring to the motor.

6.1 Installing Output Contactors (Optional)

Output contactors provide a positive means of disconnecting the motor from the drive.

If the application requires the use of output contactors, contact Reliance Electric for

assistance.

6.2 Installing Mechanical Motor Overload Protection

(Optional)

To provide the motor with overload protection, local, national, and international codes

(e.g., NEC/CEC) require one of the following:

A motor thermostat be installed internal to the motor.

An electronic thermal motor overload relay, sized to protect the motor, be installed
between the motor and the drive’s output terminals.

Note, however, that temperature measuring devices integral to the motor are the best

way to thermally protect AC motors under all conditions. Parameter P.040 must be

enabled to provide overload protection. Refer to the GV3000/SE Software Start-Up

and Reference manual for more information.

In multiple-motor applications (V/Hz regulation only), each motor must have its own

user-supplied overload protection.

6.3 Installing Output Wiring from the Drive Output

Terminals to the Motor

Use the following steps to connect the AC output power wiring from the drive to the

motor:
Step 1. Wire the three-phase AC output power motor leads by routing them

according to drive type. Refer to figures 4.1 to 4.7. Tables 3.3 to 3.8 contain

the recommended power wiring sizes.

Do not route more than three sets of motor leads through a single conduit.

This will minimize cross-talk that could reduce the effectiveness of noise

reduction methods. If more than three drive/motor connections per conduit

are required, shielded cable must be used. If possible, each conduit should

contain only one set of motor leads.