Installation/Wiring

1-7

Power Connection for 1000A and 1600A DC SCR Precharge Modules

Figure 1.5

shows typical locations of bus bars and terminals on 1000A and

1600A DC SCR Precharge Modules for customer wiring.

Figure 1.5 Bus Bar and Terminal Locations for Wiring 1000A and 1600A Modules

Table 1.C Power Connection Specifications for 1000A and 1600A Modules

Item Name

Amps Bus Bars

(1)

(1)

Input/output power bus bar connections require the use of either lug-type connectors to terminate field-installed
conductors or bus bars.

Holes

DC Bus +DCin

1000

76.2mm x 12.7mm (3.0 x 0.5 in.)
4 holes x 12.7mm (0.5 in.)

2 slots: 10mm x 20mm
(0.4 x 0.8 in.)

1600

76.2mm x 12.7mm (3.0 x 0.5 in.)
4 holes x 12.7mm (0.5 in.)

2 slots: 10mm x 20mm
(0.4 x 0.8 in.)

DC Bus +DCout

1000

76.2mm x 12.7mm (3.0 x 0.5 in.)
4 holes x 12.7mm (0.5 in.)

2 slots: 10mm x 20mm
(0.4 x 0.8 in.)

1600

76.2mm x 12.7mm (3.0 x 0.5 in.)
4 holes x 12.7mm (0.5 in.)

2 slots: 10mm x 20mm
(0.4 x 0.8 in.)

Protective Earth (GND)

1000

Bolt M10 x 25mm (0.984 in.)

Torque 10Nm (88 lb-in.)

1600

Bolt M10 x 25mm (0.984 in.)

Torque 10Nm (88 lb-in.)

Control Terminal Blocks

Refer to

Table 1.D on page 1-8

.

GND

+DCin

HK

G

DANGER

DANGER

CAN CAUSE SHOCK
BURNS, OR DEATH

SURFACES

MAY BE HOT

REMOTE
SOURCE

+DCout