2-2

Start-Up / Troubleshooting

Start-Up

Before Applying Power to the DC SCR Precharge Module

1. Verify that a minimum of one drive is connected to the DC bus. See

Minimum Capacitance on page 1-4

for details.

2. Verify that all inputs are connected to the correct terminals and are

properly torqued.

3. Using an ohmmeter or other continuity testing device, verify that shorts

do not exist between the “+DCin,” “+DCout,” and “-DC” terminals.

4. Verify that AC line power at the disconnect device is within the rated

value of the DC SCR Precharge Module. See

Appendix A

for product

electrical specification.

5. Verify that control power voltage is correct.

6. Verify that the enable precharge relay coil “CR” is correctly wired.

7. Verify that these two outputs are correctly wired:

DC SCR Precharge Overtemperature (TB2-9 and TB2-10)

Precharge Enable (TB2-6 and TB2-7)

These NC (normally closed) and NO (normally open) contacts are used
to set alarms and to stop the drive(s). Verify that they have been wired
correctly according to the user’s specification. Refer to

Figure 1.8 on page 1-10

or

Figure 1.9 on page 1-11

.

8. Verify that the “W1”, “W2,” and “W3” jumpers on the Precharge Control

Board A2 are set to the positions shown in

Table 2.A

.

Jumper

Function

W1

System control voltage selection

W2

Interlock enable/bypass

W3

Handshake normal/bypass

Table 2.A A2 Precharge Board Jumper Settings

9. Verify that the jumpers between control terminals TB2A-1 and TB2A-3,

and TB2A-2 and TB2A-4 are present.

Important: When supplying 24 VDC control power, these jumpers must

be removed from the terminals on TB2A, and 120 VAC
power must be wired to terminals TB2A-3 and TB2A-4.

(W1) JMP1

(W2) JMP2

(W3) JMP3

For PowerFlex 700H/700S Drive Applications

24 VDC

1-2

INTLK

1-2

X

NORMAL

1-2

X

120 VAC

2-3

X

BYPASS

2-3

BYPASS

2-3

For 1336 PLUS II Drive Applications

24 VDC

1-2

INTLK

1-2

NORMAL

1-2

120 VAC

2-3

X

BYPASS

2-3

X

BYPASS

2-3

X