Start-Up / Troubleshooting

Troubleshooting

Table 2.B

provides information for troubleshooting the DC SCR Precharge

Module.

Table 2.B Possible Symptoms and Corrective Actions

Symptom

Cause/Indication

Corrective Action

DC output voltage loss

DC bus:

• Short circuit or

• Low line

1. Check 3-phase AC incoming power for

undervoltage or phase loss.

2. Check the protection Precharge fuse F1.

3. After precharge is completed, verify that

the values of the “+DCin” and “+DCout”
voltages are within 1 volt.

4. Contact your local RA Sales Office.

Loss of 120 VAC or 24
VDC supply voltage

1. Verify 120 VAC or 24 VDC supply input

voltage is present at control terminals
TB2A-1 and TB2A-2.

2. Enable the contactor function.

3. Contact your local RA Sales Office.

Heat sink overtemperature
(contacts TB2A-9 and
TB2A-10 have opened)

Heat sink temperature
exceeds maximum rating

1. Verify that the maximum ambient

temperature has not been exceeded.

2. Check Overtemperature Switch “T” at

control terminals TB2A-9 and TB2A-10
that has normally closed contacts.

3. Verify 120 VAC supply input voltage at

control terminals TB2A-3 and TB2A-4.

4. Verify fan for correct operation. Airflow

should be outward from the unit.

5. Check for excess load on the DC SCR

Precharge Module.

6. Check for proper spacing around the DC

SCR Precharge Module.

7. Contact your local RA Sales Office.