Control wiring requirements, Drive run interlock – Rockwell Automation 20D DC SCR Precharge Module User Manual

Page 19

Advertising
background image

Installation/Wiring

1-9

Figure 1.7 Control Terminal Block TB1A (located on precharge control board)

Control Wiring
Requirements

Important points about control wiring:

• Use Tinned-Copper wire only. Wire gauge requirements and

recommendations are based on 75°C (168°F). Do not reduce wire gauge
when using higher temperature wire.

• Wire with an insulation rating of 600V or greater is recommended.

• Control wires outside the cabinet should be separated from power wires

by at least 0.3 meters (1 foot).

Drive Run Interlock

To protect the DC SCR Precharge Module from over-temperature failure,
the normally closed contacts of the thermo-switches on the DC SCR
Precharge Module should be wired to the Drive Run interlock circuit
(“Enable Input” or “Auxiliary Input”). This will ensure that the drive(s) are
stopped if a DC SCR Precharge Module over-temperature failure occurs.

Terminal
No.

Wiring

Description

Notes

1

+DCin

(1)

(2)

(1)

Refer to

Appendix A

for contact rating.

(2)

Terminal TB1A-1 is supplied jumpered to +DCin, and TB1A-2 is supplied jumpered to +DCout.
Wiring to these terminals by the user is not required.

+DC (positive) Bus Input Power

2

-DC

(1)

(3)

(3)

Terminal TB1A-2 must be wired to -DC of the drive by the user.

-DC (negative) Bus Power

3

+DCout

(1)

(2)

+DC (positive) Bus Output Power

2

1

3

CR

TB1A

8 7 6

5

4 3 2 1

9

14

12 11 10

13