1-8

Installation/Wiring

Control Wiring and
Terminals

Terminal blocks TB1A and TB2A contain connection points for control
wiring of the DC SCR Precharge Module.

Table 1.D Control Terminal Specifications for TB1A and TB2A

Figure 1.6 Control Terminal Block TB2A (located on precharge control board)

Name

Wire Size Range

(1)

(1)

Maximum/minimum sizes that the terminals will accept – these are not recommendations.

Torque

Maximum

Minimum

Control Terminal Blocks

2.5 sq. mm
(14 AWG)

0.25 sq. mm
(22 AWG)

0.8 Nm
(7 lb.-in.)

Terminal
No.

Wiring

Description

Polarity

Notes

1

Customer-
supplied

120 VAC or
24 VDC Input

Phase

For interlocking with input system power. See

Start-Up on page 2-2

for voltage selection.

2

Neutral

3

Customer-
supplied

120 VAC

Phase

For supplying 120 VAC power to a cooling fan

4

Neutral

5

Customer-
supplied

120 VAC

Phase

From external Normally Open contact that
energizes the Precharge Control Relay “CR”

6

Customer-
supplied

Normally Open
contact

(1)

(1)

Refer to

Appendix A

for contact rating.

Output contacts from the Precharge Control
Relay “CR”

7

8

Normally Closed
contact

(1)

Output contacts from the Precharge Control
Relay CR - “Precharge Enable”

9

Customer-
supplied

Normally Closed
contact

(1)

Thermo switch’s contacts that open if the
Power Module has over-temperature failure

10
11

Spare

12

Customer-
supplied

Ground (GND)

GND

Ground for a cooling fan

3

1

2

4

5

6

7

8

10

11

12

9

F1

TB2A

1

2

Customer Side