Extension cable installation environment, Outer dimensions and part nomenclature, 1442 sensor outer dimensions and part nomenclature – Rockwell Automation 1442 Eddy Current Probe System User Manual

Page 17

Advertising
background image

Rockwell Automation Publication ICM-UM004C-EN-E - February 2014

17

Installation

Chapter 1

Extension Cable Installation Environment

Install the extension cable in a location that satisfies the following environmental
and installation conditions.

Outer Dimensions and Part
Nomenclature

1442 Sensor Outer Dimensions and Part Nomenclature

5 mm Sensor

L1 = Unthreaded length

L2 = Case length

L3 = Cable length

Feature Specification

Ambient temperature

Cable must be in a range of -35…177 °C (-31…350 °F) when devices are
operating.
Connector must be in a range of -35…125 °C
(-31…257 °F) when devices are operating.
ATEX applications must be in a range of -35…80 °C (-31…176 °F) when devices
are operating.
CSA applications must be in a range of -35…85 °C (-31…185 °F) when devices
are operating.

Ambient humidity

Must be in a range of 30…95% RH (noncondensing) when devices are operating.