2 - maintenance and inspection, Periodic inspection intervals, Unit life – Rockwell Automation 1442 Eddy Current Probe System User Manual

Page 39: Chapter 2, Maintenance and inspection, Periodic inspection intervals unit life, Chapter

Advertising
background image

Rockwell Automation Publication ICM-UM004C-EN-E - February 2014

39

Chapter

2

Maintenance and Inspection

This chapter describes the maintenance and inspection procedures for the unit.

Periodic Inspection Intervals

To maintain performance and secure system stability of the unit, inspect the
system and its mounts for corrosion, properly-tightened or torqued fittings and
connections, and component conditions annually. Check sensor gap settings
annually and at any time measurements become suspect.

Refer to Set Gap Voltage

on page 36

.

Unit Life

Plan to replace eddy current probe systems approximately every 10 years.

The following is a flowchart for determining when a replacement is required.

IMPORTANT

Ten years is a general guideline for replacement. If otherwise undisturbed,
eddy current probe systems deteriorate over time due to temperature and
erosion. The deterioration rate for sensors, extension cables, and drivers
depends on the specific environmental conditions to which each
component is subjected.

Calibration

(Static characteristic data collection)

The margin for error satisfies the specifications.
(Thrust, Rotations --> sensitivity)
(Vibration, Eccentric --> scale factor)

Verify the installation, reset the gap and/or troubleshoot
the system per this instruction.
Does the system performance satisfy the specifications?

Replacement is recommended.

Continue to use the unit.

Continue to use the unit after adjustment.

Yes

Yes

No

No

Advertising