Section 6–Device Configuration

ATC200-LITE-USB Teletilt

®

RET System

6-5

October

2014

Bulletin 639536 • Revision L

Figure 6-5. Confirmation of Configuration Changes to Device.

10. When the configuration process is complete, a pop-up dialog box will display the results. Nor-

mally, the dialog box will show that the changes were successfully sent to the device (Figure
6-5). However, if the configuration process was unable to communicate with the actuator for any
reason, a failure message will appear.

If this occurs, ensure that all cables and connectors to the actuator are properly connected, and
that the system is still properly powered up. Also, verify that the actuator is present in the
Device Information list, and that it does not have a status reading of Not Reporting. A status
of Not Reporting indicates that connectivity to the actuator has been lost. After verifying that
each of these items are correct, repeat the configuration process.

11. Click OK (Figure 6-4) to dismiss the pop-up dialog box. The main screen will display the results

of the device configuration.

12. Note that not all of the items that were configured are displayed on the main screen. To verify

that each of the items configured were set correctly, select the device in the Device Informa-
tion
list and click Edit Selected to review each item (Figure 6-1). Click the Cancel button on
the Device Configuration screen when finished with verification.