SEQUENCE OF OPERATION
Normal Operation

1. When the thermostat call for heat, the vent damper

will open (see paragraphs 17A through 17D). The

circulator is started through a relay and at the same

time the gas valve is energized allowing main gas

flow and ignition of main burners.

2. Where condensation of flue gas is encountered in

boiler flues a reverse acting circulator control should

be installed to stop the circulator before the boiler

water temperature drops to that which flue gas

condensation may occur.

3. After the thermostat is satisfied the main valve will

close and main burner flames will be extinguished.

The vent damper will close (see paragraph 17E).

SAFETY ShUTDOWN

1. high Limit Switch
In the event excessive boiler water temperature is

developed the high limit switch will open

interrupting power to the gas valve. The main

burners will be extinguished immediately, and the

vent damper will close at the same time, but the

circulator will continue to operated. Normal

operation will be resumed when the boiler water

temperature drops to a point where the high limit

switch closes.

Figure 11: Wiring Diagram,  Volt Standing Pilot and Intermittent Circulation

2. Blocked vent Switch
In the event excessive blockage in the vent system is

developed the blocked vent switch will open

interrupting power to the gas valve. The main

burners will be extinguished immediately, the

circulator will continue to operate, and the vent

damper will remain open until the thermostat is

turned off. The source of blockage must be

corrected by trained and skilled personnel from a

qualified service agency before resetting switch.

3. Flame Rollout Switch
In the event excessive blockage in the boiler section

flue passageways is developed the flame rollout

switch will open interrupting power to the gas valve.

The main burners will be extinguished immediately,

the circulator will continue to operate and the vent

damper will remain open until the thermostat is

turned off. If the flame rollout switch is activated do

not attempt to place the boiler in operation. The

source of blockage must be corrected and the flame

rollout switch replaced by trained and skilled

personnel from a qualified service agency.

4. Pilot
The thermocouple proves pilot flame and in the

absence of such within 45-90 seconds causes the

combination gas valve, which is equipped with a

100% shut-off provision, to be de-energized, thus,

preventing main gas or pilot gas flow.