Notice – Burnham Series 2B User Manual

Page 23

Advertising
background image

3

B. See Figure 22 for continuous ignition system

(standing pilot).

4.

ChECK GAS INPUT RATE TO BOILER

NOTICE

USA boilers built for installation at altitudes greater

than 2,000 feet above sea level have been specially

orificed to reduce gas input rate 4 percent per 1,000 feet

above sea level per the National Fuel Gas Code, NFPA

54/ANSI Z223.1, Section 8.1.2 and Appendix F.

Canadian boilers' orifice sizing is indicated on the rating

label. High altitude boiler models are identifiable by

the fourth digit after the dash in the model number. 2:

0-2000', 4 or 5: above 2000'.
A. Input Rate and Maximum Inlet Pressure shown on

Rating Label must not be exceeded. Inlet pressure

must not be lower than minimum inlet pressure

shown on Rating Label.

B. All Rate checks and all adjustments are to be made

while boiler is firing - all other appliances connected

to the same meter as the boiler must be off.

C. With boiler off, water Manometer or water column

gauge should be connected to a shut-off valve

installed in the 1/8" outlet pressure tap in the gas

valve (see Figure 19). By installing gas valve

upstream of manometer, gas pressure can be

introduced gradually - without shut-off valve, surge

of pressure when boiler is turned on, could blow

liquid out of manometer. Replace plug in gas valve

when rate check is finished.

D. LP Gas Input:
Adjust Regulator on Gas valve so that manifold

pressure is 10 inches water column. Turning

Regulator Adjusting Screw Clockwise increases

pressure. Counterclockwise rotation decreases

pressure.

E. Natural Gas Input

1. Appx. Input - Adjust regulator on Gas valve so

that manifold pressure is three and a half (3½)

inches water column. Turning Regulator

Adjusting Screw Clockwise increases pressure,

Counterclockwise rotation decreases pressure. If

Figure 3: 0mm Main Burner Flame

Figure : 1 Inch Main Burner Flame

more accurate check on input is necessary see

(2) below.

For minor input changes readjust Regulator Gas

valve to increase or decrease manifold pressure

to obtain corresponding increase or decrease in

gas input. If it is necessary to increase manifold

pressure more than 0.3" of water to obtain rated

input, remove orifices and drill one size larger.

Reinstall and recheck input rate.

2. Additional Check on Input - Since input is a

function of heating value, specific gravity, and

volume of gas flow contact your utility for the

first two items in order to utilize the formula

below. The gas meter should then be clocked for

three (3) minutes with stop watch and

substituting the appropriate values in the formula

below, determine what the gas flow should be in

this 3 minute period to give the input shown on

the Rating Label:

Gas Input

=

Btuh Input

(cu. ft.)

Heating

Multiplier

per 3 min.

Value

X

from

of Gas

Table 3

(Btu / cu. ft.

5.

MAIN BURNER FLAMES should have a clearly

defined inner cone (see Figure 23 or 24) with no yellow

tipping. Orange-yellow streaks caused by dust should

not be confused with true yellow tipping.

The main burners in this boiler will not operate cleanly

or efficiently if they are contaminated with dirt and/or

construction dust. Burners should be cleaned and the

combustion chamber vacuumed following instructions

in Section Iv. Service.

6.

ChECK PILOT BURNER FLAME.

A. Continuous Ignition (Standing Pilot)
LP gas Models 202 and 202x. See Figure 25.
Natural gas Models 202 through 206 and 207 with

1" diameter burners. See Figure 25.