Burnham Series 2B User Manual

Page 14

Advertising
background image

1

Figure 1: Wiring Diagram, Electronic Ignition (EI), Intermittent Circulation

SEQUENCE OF OPERATION
NORMAL OPERATION

1. When the thermostat calls for heat, the relay is

energized. The circulator starts and the vent damper

opens (see Paragraphs 17A through 17D). When the

damper blade reaches the fully open position, the

ignition module is energized opening the pilot valve

and energizing the igniter to ignite the pilot burner.

2. Sensor proves presence of pilot flame. Main valve

opens to ignite main burners.

3. The burners and circulator will operate

simultaneously until the thermostat is satisfied.

4. After thermostat is satisfied, ignition module is de-

energized, extinguishing pilot and main flame. Vent

damper closes (see paragraph 17E).

SAFETY ShUTDOWN

1. Limit: Automatically interrupts main burner

operation when water temperature exceeds set point.

Maximum allowable temperature is 250°F. Normal

operation resumes when water temperature falls

below set point.

2. Blocked vent Switch: Automatically interrupts

main burner operation when excessive vent system

blockage occurs. Control is a multiple use device. If

blocked vent switch is activated do not attempt to

place boiler in operation. Correct source of blockage

and reset blocked vent switch.

3. Flame Roll-out Switch: Automatically interrupts

boiler operation when flames or excessive heat are

present in vestibule. Control is single use device. If

flame roll-out switch is activated do not attempt to

place boiler in operation. Correct source of blockage

and replace flame roll-out switch.

4. Igniter/Sensor: senses pilot flame and causes

ignition module to turn off main burner and pilot

burner gas flow should pilot burner flame

extinguish. Five to six minutes after shutdown,

ignition module restarts ignition sequence.

5. For Electronic Ignition Trouble Shooting Guide, see

Page 25 of this manual.

Advertising