Caution – Burnham Series 2B User Manual

Page 20

Advertising
background image

0

e. Reconnect pilot tubing and check pipe and

fittings from meter to combination Gas

valve for leaks using soap solution or other

approved method.

2. Electronic Ignition Models (Suffix I):

a. Turn "ON" electric switch serving boiler.
b. Open Manual Shut-off valve upstream of

Combination Gas valve.

c. Loosen or remove Inlet Pressure Tap Plug in

Combination Gas valve and when purging is

complete, tighten or replace plug. See Figure

19.

d. Check pipe and fittings from meter to

Combination Gas valve using soap solution

or other approved methods.

CAUTION

e. Test gas piping and connections between

Combination Gas valve and manifold,

orifices, and pilot piping for leaks after

boiler is operating. Use soap solution or

other approved method.

3.

INSTRUCTIONS TO PUT ThE BOILER IN

OPERATION.
A. See Figure 20 for electronic ignition (EI).

Electronic Ignition Modules with LED indicators.

Table 5 cross-references the ignition module

terminal designations to the ignition terminal

numbers in the wiring ladder diagrams. The yellow

LED indicates the status of the flame, see Table 6.

The green LED indicates the status of the system,

see Table 7. See Figure 21 for LED locations. See

Figure 28 for Troubleshooting Guide.

Figure 1: LED Locations

Ignition Module

Terminal Designation

Wiring Ladder Diagram

Terminal Number

MV

1

MV/PV

2

PV

3

GND

4

24V (GND)

5

24V

6

SPARK

9

Table : Ignition Module Terminal Cross-

Reference

Yellow LED Flash

Code

a

Indicates

Recommended Service Action

Heartbeat

Normal Flame Signal

N/A

2

Weak Flame Signal -

System will operate reliably but flame signal is less than

desired.

Note: This indication may flash temporarily during or

shortly after lightoff on some applications.

Perform routine maintenance to

assure optimum flame signal.

1

Marginal Flame Signal (less than 1.1 µA) -

System may not operate reliably over time. Service call

recommended.

Note: This indication may flash temporarily during or

shortly after lightoff on some applications.

Check gas supply, pilot burner, flame sense

wiring, contamination of flame rod, burner

ground connection.

OFF

No Flame or Flame Signal -

below minimum threshold for system

operation.

N/A

a

Flash Code Descriptions

- Heartbeat: Constant ½ second bright, ½ second dim cycles.

- The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats sequence.

Table : Yellow LED Flame Codes