Burnham Series 2B User Manual

Page 5

Advertising
background image



e. For boiler located in a building of other than

unusually tight construction, adequate

combustion and ventilation air is normally

provided by fresh air infiltration through

cracks around windows and doors.

f. For boiler located

in building of unusually

tight construction, provide outdoor air

through two permanent openings which

communicate directly or by duct with the

outdoors or spaces (crawl or attic) freely

communicating with the outdoors. Locate

one opening within 12 inches (30.5cm) of

top of space. Locate remaining opening

within 12 inches (30.5cm) of bottom of

space. Minimum dimension of air opening is

3 inches (7.6cm). Size each opening per

following:

i. Direct communication with outdoors.

Minimum free area of 1 square inch

(6.5cm

2

) per 4,000 Btu per hour input of

all equipment in space.

ii. vertical ducts. Minimum free area of 1

square inch (6.5cm

2

) per 4,000 Btu per

hour input of all equipment in space. Duct

cross-sectional area shall be same as

opening free area.

iii. Horizontal ducts. Minimum free area of 1

square inch (6.5cm

2

) per 2,000 Btu per

hour input of all equipment in space. Duct

cross-sectional area shall be same as

opening free area.

g. ventilation Duct Louvers and Grilles. Equip

outside openings with louvers to prevent

entrance of rain and snow, and screens to

prevent entrance of insects and rodents.

Louvers and grilles must be fixed in open

position or interlocked with equipment to

open automatically before burner operation.

Screens must not be smaller than ¼ inch

mesh.

Consider the blocking effect of louvers,

grilles and screens when calculating the

opening size to provide the required free

area. If free area of louver or grille is not

known, assume wood louvers have 20-25

percent free area and metal louvers and

grilles have 60-75 percent free area.

8.

CONNECT GAS SERvICE from Meter to gas control

assembly in accordance with Local Piping Codes and

requirements of Gas Company, see Figure 1. They may

require piping of larger size than Control Assembly

Connection, especially if run from meter is long or

includes several elbows. (See Figure 1 for size of Gas

Connection to gas control assembly).

volume [ft³](m

3

) = Length [ft](m) x Width

[ft](m) x height [ft](m)

b. Determine Total Input of all appliances in

space. Round result to nearest 1,000 Btu per

hour (Btuh).

c. Determine type of space. Divide volume by

Total Input.

i. If result is greater than or equal to 50 ft³

(1.4m3) per 1,000 Btuh, space is

considered an unconfined space.

ii. If result is less than 50 ft³ (1.4m3) per

1,000 Btuh, space is considered a confined

space.

d. Determine building type. A building of

unusually tight construction has the

following characteristics:

i. Walls and ceiling exposed to outside

atmosphere have a continuous water vapor

retarder with a rating of 1 perm or less

with openings gasketed and sealed, and

ii. Weather-stripping has been added on

openable windows and doors, and

iii. Caulking or sealants applied in joints

around window and door frames, between

sole plates and floors, between wall-

ceiling joints, between wall panels, at

plumbing and electrical penetrations, and

at other openings.

Figure : Minimum Clearances

Advertising