WARNING

Failure to properly install and use this Blocked

Vent Switch may result in property damage,

personal injury or loss of life.

12

. TO MEET FEDERALLY MANDATED

EFFICIENCIES, ThIS BOILER MUST BE

EQUIPPED WITh A vENT DAMPER.

OPEN ThE vENT DAMPER CARTON and remove

the Installation Instructions. READ ThE INSTALLA-

TION INSTRUCTIONS ThOROUGhLY before

proceeding.

The automatic gas control valve supplied on each Series

2™ boiler provides the redundancy referenced in the

vent damper Installation Instructions.

CAUTION

Do not use one vent damper to control two heating

appliances.

A. The vent damper should be the same size as the

outlet of the Draft hood. (See Figure 1) Unpack the

damper carefully - DO NOT FORCE IT CLOSED!

Forcing the damper may damage the gear train and

void the warranty. The damper assembly includes a

prewired connection harness for use on all 24v

Standing Pilot or electronic ignition control systems.

B. Mount the vent damper assembly after the draft

hood, as close to the draft hood as practicable

without modification to the draft hood or vent

damper. (Refer to Figure 7 and to instructions

packed with the vent damper for specific

instructions). This is a must for the wiring harness to

fit and the damper position indicator to be visible to

the users.

Figure : Plug-in Damper Installation

NOTICE

Provide adequate clearance for servicing.

WARNING

Provide " (1.cm) minimum clearance between

damper and combustible construction.

C. Install the 90° BX connector attached to the flexible

conduit in the 7/8" knockout on the left side of the

jacket. Plug the factory wired vent Damper harness

into the polarized receptacle. Install a cable clamp

around the flexible conduit and attach to the Jacket

top panel. (See Figure 7).

NOTICE

Please refer to the specifications, installation

instructions and troubleshooting guide packed

in the vent damper carton for complete detailed

installation instructions. Also refer to Figure  in

this manual.

D Continuous Ignition (Standing Pilot) Only. Remove

knockout from vent damper blade.

E. Size 202 Only. Install 4" x 3" reducing fitting on

vent damper outlet.

13.

INSTALL vENT CONNECTOR from reducing

fitting (202 Only), draft hood or damper to chimney, see

Figure 8.